描述
Model Number | FX3U-4AD-TC-ADP |
Number of input points | 4ch |
Input signal | Thermocouple type K or J JIS C 1602-1995 |
Rated temperature range | • Type K: -100°C to +1000°C • Type J: -100°C to +600°C |
Digital output | • Type K: -1000 to +10000 • Type J: -1000 to +6000 |
Resolution | • Type K: 0.4°C • Type J: 0.3°C |
Overall accuracy | • Ambient temperature: 25°C±5°C ±0.5% for full scale • Ambient temperature: 0°C to 55°C ±1.0% for full scale |
Time required for conversion |
• FX3U/FX3UC Series PLC : 200μs (Data updated every scan time.) • FX3S/FX3G/FX3GC Series PLC : 250μs (Data updated every scan time.) |
Insulation method | • The photocoupler is used to insulate the analog input area from the PLC. • The DC/DC converter is used to insulate the power supply from the analog inputs. • Channels are not insulated from each other. |
Number of I/O points occupied |
0 points (This number of points is not related to the maximum number of input/output points of the PLC.) |